Customization: | Available |
---|---|
Breaking Capacity: | Medium Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item
|
Weight (KG)
|
High*Width*Deep(mm)
|
Motor input power (W)
|
Closing spring (mm)
|
Matched vacuum circuit breaker opening current (kA)
|
CT19BN | 40 | 440*360*160 | 250 | Φ10 | 31.5 |
CT19BW | 45 | 550*360*160 | 250 | Φ10+Φ6 | 31.5 |
2.Closing/Opening electromagnet adopt solenoid electromagnet, technical parameter as Table:
Rated operate voltage (V) |
AC110 | AC220 | DC110 Close | DC110 Open | DC220 Close | DC220 Open |
Rated operating current(A) |
4.3 | 3.8 | 2.3 | 4 | 1.16 | 2 |
Rated power (W) |
<437 | <836 | <253 | <440 | <255 | <440 |
Coil resistance at 20°C (Ω) |
8.5±0.5 | 19.2±1.2 | 47±2.8 | 27.5±1.7 | 190±5 | 106±3 |
Normal operating voltage range |
Open at 65%~120% rated operate voltage; do not open when less than 30% rated operate voltage |
|||||
Close at 85%~110% rated operate voltage; do not close when less than 30% rated operate voltage |
3.Mechanism output angle 50-55 degree.
4.The combination and code of release: 104,114,1114,1134,400