Item
|
ZYJ220-53-216 | ZYJ110-53-216 | ZYJ48-53-216 | ZYJ24-53-216 |
Rated operate voltage (V)
|
DC220 | DC110 | DC48 | DC24 |
Rated power (W)
|
40 | 40 | 40 | 40 |
Normal operating voltage range (V)
|
85%-110% | 85%-110% | 85%-110% | 85%-110% |
Rated operating current (A)
|
0.5 | 1.0 | 1.8 | 4.6 |
Motor energy storage time (S)
|
≤8 | ≤8 | ≤8 | ≤8 |
2.Closing/Opening electromagnet adopt solenoid electromagnet, technical parameter as Table:
Rated operate voltage (V)
|
DC220 | DC110 | DC48 | DC24 |
Rated operating current (A)
|
1.69 | 3.4 | 10 | 11.5 |
Rated power (W)
|
372 | 374 | 480 | 276 |
Coil resistance at 20°C (Ω)
|
125 | 33 | 4.8 | 1.2 |
Normal operating voltage range |
Open at 65%~120% rated operate voltage; do not open when less than 30% rated operate voltage
|
|||
Close at 85%~110% rated operate voltage; do not close when less than 30% rated operate voltage
|
3.Mechanism output angle 44 degree.