Customization: | Available |
---|---|
Breaking Capacity: | Medium Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1.Energy storage motor adopt unidirectional permanent DC motor, technical parameter as Table:
Item |
ZYJ220-53-216 | ZYJ220-53-216 | ZYJ220-53-216 | ZYJ220-53-216 |
Rated operate voltage (V) |
DC220 | DC110 | DC48 | DC24 |
Rated power (W) |
40 | 40 | 40 | 40 |
Normal operating voltage range |
85%-110% | 85%-110% | 85%-110% | 85%-110% |
Rated operating current(A) |
0.5 | 1.0 | 2.3 | 4.6 |
Motor energy storage time (S) |
≤8 | ≤8 | ≤8 | ≤8 |
2.Closing/Opening electromagnet adopt solenoid electromagnet, technical parameter as Table:
Rated operate voltage (V)
|
AC220 | AC110 | DC200 | DC110 | DC48 | DC24 |
Rated operating current(A)
|
1.36 | 3.60 | 2 | 4 | 6.7 | 13 |
Rated power (W)
|
299 | 396 | 440 | 440 | 320 | 320 |
Coil resistance at 20°C (Ω)
|
54 | 10.3 | 106 | 27.5 | 7.2 | 2 |
Normal operating voltage range
|
Open at 65%~120% rated operate voltage; do not open when less than 30% rated operate voltage
|
|||||
Close at 80%~110% rated operate voltage; do not close when less than 30% rated operate voltage
|
3.Manual energy storage is operated by the handle allocated with the mechanism, the operating force less than 100 (N.m)
4.Mechanism output angle 43 degree
5.Mechanism net weight: CTW-D: 25kg CTW-S: 20kg
6.The auxiliary switch contacts with the mechanism can pass through continuous current 10A (AC220V) and 3A (DC220V)
7.Limit switch adopt CSK11-A-33 magnetic blowout switch. The continuous current through that the contact can pass: 8A (AC380V); 3A (DC220V)