Customization: | Available |
---|---|
Breaking Capacity: | Medium Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Working Condition
1.Energy storage motor adopt unidirectional permanent DC motor, technical parameter as Table:
Item |
53ZY-CJD01B | 53ZY-CJD02B | 53ZY-CJD03B | 53ZY-CJD04B |
Rated operate voltage (V) |
DC220 | DC110 | DC48 | DC24 |
Rated power (W) |
40 | 40 | 40 | 40 |
Normal operating voltage range |
85%-110% | 85%-110% | 85%-110% | 85%-110% |
Rated operating current(A) |
0.5 | 1.0 | 1.8 | 3.6 |
Motor energy storage time (S) |
≤8 | ≤8 | ≤8 | ≤8 |
2.Closing/Opening electromagnet adopt solenoid electromagnet, technical parameter as Table:
Rated operate voltage (V) |
DC220 | DC110 | DC48 | DC24 |
Rated operating current(A) |
1.69 | 3.4 | 6.8 | 13.3 |
Rated power (W) |
372 | 367 | 165 | 320 |
Coil resistance at 20°C (Ω) |
130 | 33 | 3.5 | 1.8 |
Normal operating voltage range |
Open at 65%~120% rated operate voltage; do not open when less than 30% rated operate voltage |
|||
Close at 85%~110% rated operate voltage; do not close when less than 30% rated operate voltage |
3.Mechanism main technical parameter as Table:
No.
|
Item
|
Unit
|
Data
|
1 |
Mechanism output angle
|
Degree
|
40 |
2 |
Manual energy storage operating force
|
N | <400 |
3 |
Rated operating current of auxiliary switch
|
A | 10 |
4 |
Rated operating current of terminals
|
A | 10 |
5 |
Rated operating current of limit switch (DC)
|
A | 2 |
6 |
Mechanical life
|
Times | 10000 |